What is the definition of power factor?

2 years ago 1509 0 News

電路.jpg


Definition of Power Factor


The power factor is equal to the real or true power P in watts (W) divided by the apparent power |S| in volt-ampere (VA):

PF = P(W) / |S(VA)|

PF - power factor.

P - the real power in watts (W).

|S| - apparent power - the magnitude of the complex power in volt·amps (VA).

Power factor calculations

For sinusoidal current, the power factor PF is equal to the absolute value of the cosine of the apparent power phase angle φ (which is also is impedance phase angle):

PF = |cos φ|

PF is the power factor.

φ is the apparent power phase angle.

The real power P in watts (W) is equal to the apparent power |S| in volt-ampere (VA) times the power factor PF:

P(W) = |S(VA)| × PF = |S(VA)| × |cos φ|

When the circuit has a resistive impedance load, the real power P is equal to the apparent power |S| and the power factor PF is equal to 1:

PF(resistive load) = P / |S| = 1

The reactive power Q in volt-amps reactive (VAR) is equal to the apparent power |S| in volt-ampere (VA) times the sine of the phase angle φ:

Q(VAR) = |S(VA)| × |sin φ|

Single phase circuit calculation from real power meter reading P in kilowatts (kW), voltage V in volts (V), and current I in amps (A):

PF = |cos φ| = 1000 × P(kW) / (V(V) × I(A))

Three phase circuit calculation from real power meter reading P in kilowatts (kW), the line to line voltage VL-L in volts (V), and current I in amps (A):

PF = |cos φ| = 1000 × P(kW) / (√3 × VL-L(V) × I(A))

Three-phase circuit calculation from real power meter reading P in kilowatts (kW), the line to line neutral L-N in volts (V), and current I in amps (A):

PF = |cos φ| = 1000 × P(kW) / (3 × VL-N(V) × I(A))

Power factor correction

Power factor correction is an adjustment of the electrical circuit in order to change the power factor near 1.

A power factor near 1 will reduce the reactive power in the circuit and most of the power in the circuit will be real power. This will also reduce power line losses.

The power factor correction is usually done by adding capacitors to the load circuit, when the circuit has inductive components, like an electric motor.

Power factor correction calculation

The apparent power |S| in volt-amps (VA) is equal to the voltage V in volts (V) times the current I in amps (A):

|S(VA)| = V(V) × I(A)

The reactive power Q in volt-amps reactive (VAR) is equal to the square root of the square of the apparent power |S| in volt-ampere (VA) minus the square of the real power P in watts (W) (Pythagorean theorem):

Q(VAR) = √(|S(VA)|2 - P(W)2)

The reactive power Q in volt-amps reactive (VAR) is equal to the square of voltage V in volts (V) divided by the reactance Xc:

Q(VAR) = V(V)2 / XC = V(V)2 / (1 / (2πf(Hz)·C(F))) = 2πf(Hz)·C(F)·V(V)2

So the power factor power cable correction capacitor in Farad (F) that should be added to the circuit in parallel is equal to the reactive power Q in volt-amps reactive (VAR) divided by 2π times the frequency f in Hertz (Hz) times the squared voltage V in volts (V):

C(F) = Q(VAR) / (2πf(Hz)·V(V)2)

Tags:
power factor
INQUIRY
主站蜘蛛池模板: 草碰在线| 国产精品无码久久久久成人影院 | 国产免费无码一区二区三区 | 亚洲成年女人av毛片性性教育 | 精品人妻无码一区二区三区竹菊影视 | 国内盗摄视频一区二区三区 | 看真人视频a级毛片 | 性做久久久久久久久 | 成人爱爱 | 99热这里精品 | 99久久免费精品国产男女高不卡 | 色香欲综合成人免费视频 | 日韩免费视频一区二区 | 亚洲成A人一区二区三区 | 一级做a爰片性色毛片 | 二人午夜免费观看在线视频 | 亚洲日韩欧美一区二区三区 | 日日噜噜噜夜夜爽爽狠狠小说 | 亚洲成人资源在线 | 国内偷拍久久 | 韩国一级淫一片免费放 | 国产乱码久久久久久 | av免费看国产 | 中文字幕乱码亚洲影视 | 在线超碰免费 | 中文字幕12页 | AV永久天堂一区二区三区香港 | 7777888色淫网站免费视频 | 欧美城天堂网地址 | 韩日av一区二区三区 | 国产精品久久久久久无码人妻 | 精品综合久久久久久99粉芽 | 一出一进一爽一粗一大视频免费的 | 在线播放亚洲视频 | 一级网站在线观看 | 免费观看做爰视频ⅹxx午夜 | 国产精品老熟女一区二区三区 | 亚洲s色大片在线观看 | 国产精品久久久久久久久婷婷 | 一夜新娘第三季在线观看 | 久久午夜羞羞影院免费观看 |