How do you determine if the XLPE cable is actually pierced?

2 years ago 2119 0 News

Insulation layer.jpg


Reasons and Methods for Determining Whether XLPE Cables are Damaged


Power cables are buried underground, and once a fault occurs, it is very difficult to find, often taking hours or even days, which not only wastes a lot of manpower and material resources but also causes incalculable power outage losses.

How to accurately, quickly, and economically find cable faults has become a growing concern for the power supply sector.

The cable fault situation and buried environment are complex and changeable. Testers should be familiar with the buried direction of the cable and the environment, to determine the exact nature of the cable fault, select the appropriate

instrument and measurement methods, and work according to certain procedures, in order to successfully measure the cable fault point.


XLPE Cable Failure Causes

Understanding the causes of cable faults is important to reduce damage to the cable and to quickly determine the point of failure.

The causes of cable faults can be broadly categorized as follows:

  • Mechanical Damage

    Cable failures caused by mechanical damage account for a large percentage of cable accidents. Some mechanical damage is so minor that it does not cause a fault at the time, but the damaged area develops into a fault only after several months or even years. The main causes of mechanical damage to the cable are as follows:

    1 Damage During Installation

    Inadvertent touching of the cable during installation, the mechanical traction force being too large and straining the cable, or the cable being damaged by excessive bending.

    2 Directly Damaged by External Forces

    After installation on the cable path or near the cable for urban construction, the cable is directly damaged by external forces.

    3 Driving Process Damage

    The vibration or impact load of the traveling vehicle can cause the underground cable lead (aluminum) package cracking damage.

    4 Damage Caused by Natural Phenomena

    Such as intermediate joints or terminal heads inside the insulation rubber expansion and expansion of the shell or cable sheath.

    Due to the natural travel of the cable, the outer skin of the cable is mounted on the mouth of the pipe or bracket abrasion.

    Excessive tension caused by land settlement, pulling off intermediate joints or conductors.

  • Cable Insulation Moisture

    Failure caused by moisture in the cable insulation.

    The main causes of cable moisture are:

    1 Water ingress due to unsealed joint box or terminal box structure or poor installation.

    2 Poorly manufactured cable with small holes or cracks in the metal sheath.

    3 The metal sheath is pierced or corroded and perforated by foreign objects.

  • Insulation Aging Deterioration

    The internal air gap of the cable insulation medium produces ionization under the action of an electric field to make the insulation drop. When the insulating medium ionizes, the air gap generates chemical products such as ozone and nitric acid, which corrode the insulation. The moisture in the insulation causes hydrolysis of the insulation fiber, resulting in insulation degradation.

    Overheating can also cause insulation aging and deterioration. The internal air gap of the cable generates electric ionization causing local overheating and carbonization of the insulation. Cable overload is a very important factor in cable overheating.

    Cables installed in cable-dense areas, cables in cable trenches and cable tunnels and other poorly ventilated places, cables worn in dry pipes, and parts of cables close to heat pipes can accelerate insulation damage due to overheating itself.

  • Overvoltage

    The atmosphere and internal overvoltage action, so that the cable insulation breakdown, forming a fault, the breakdown point is generally the presence of defects.

  • Poor Design and Manufacturing Process

    Waterproofing of intermediate joints and terminal heads, poorly designed electric field distribution, improper choice of materials, poor workmanship, and not being made according to the requirements of the regulations can cause cable head failure.

  • Cable Insulation Loss

    Oil-impregnated paper-insulated cable laying trench convexity, or in the outdoor head on the pole, due to the undulation, height disparity, the high insulating oil flow to the low.

    And make the high cable insulation performance decline, resulting in failure.


In partial discharge or high voltage tests, cross-linked circuits can break down for various reasons, but not every breakdown means that the insulation really breaks down.

It is worn with true degradation and false breakdown, respectively. Correct and effective identification of false breakdowns can improve the efficiency of the cable plant.

In case of a breakdown during the test, the insulation core should be replaced for inspection.

After replacing the insulation core, the voltage test is performed again and the voltage test results represent different situations.

In the first case, the voltage detection is normal and the cable should be confirmed to be faulty.

In the second case, the breakdown voltage gradually decreases, representing a breakdown inside the cable.

In the third case, the breakdown voltage is the same every time, which means the breakdown may occur at the end of the cable.
So how to confirm the breakdown inside the XLPE cable is false?

After the second test, we can control the partial discharge of the cable in the shielding room, increase the voltage level and observe the breakdown phenomenon, and determine the breakdown location in this way.

If the breakdown location is not at the end of the cable, the cable should be replaced, and sometimes even the qualified cable or no-load cable can be inspected. When the breakdown voltage value should be consistent with the previous one after

inspection and replacement, the cable breakdown phenomenon can be confirmed as a false breakdown.
Some cross-connected cables sent for inspection may exceed the maximum load of the experimental equipment due to their excessive length, so it must be determined whether the load is large enough before the test. Otherwise, the tripping

the phenomenon will occur during the test.

In addition, it should be noted that if the test system cannot be boosted, this may be caused by an internal short circuit in the cable insulation, which can only be confirmed by replacing the insulation core.


INQUIRY
主站蜘蛛池模板: 四虎国产在线观看 | 男人狂桶女人出白浆免费视频 | 成人综合网亚洲伊人 | 国产精品刺激 | 一本到国产在线精品国内 | 丝袜老师高潮呻吟高潮 | 亚洲综合久久久 | 视频一区二| 亚洲精品在线免费看 | 亚洲成av人的天堂在线观看 | 欧美成人aaa级毛片在线视频 | 欧美专区第一页 | 日本亲子乱子伦xxxx | 日韩有码在线观看 | 三a大片| 在线播放日韩精品 | 国产欧美一区二区三区精品酒店 | 久操免费在线视频 | 夜精品无码A片一区二区蜜桃 | 久久精品1区 | 亚洲精品成人AA片在线播 | 欧美图片第一页 | 少妇熟女高潮流白浆 | 岛国无码免费不卡av | 97色国产| 午在线亚洲男人午在线 | 老司机狠狠干 | 国产99久久久国产精品免费看 | 337p日本欧洲亚洲大胆张筱雨 | 性按摩aaaaaa视频 | 久久精品国产免费看久久精品 | 亚洲成人资源在线 | 四虎最新在线观看地址 | 国产成人精品免费视频大全 | 成人午夜在线视频 | av资源站最稳定的资源站 | 成人片黄网站A片免费 | 东京亚洲区卡不 | 日本xxxxxxxxx96| 女人19毛片一级毛片 | 亚洲国产成人一区二区精品区 |