Control cable installation measures

5 years ago 1561 0 News

In order to ensure the control cable in the event of insulation breakdown, mechanical damage or fire, reduce the scope of the spread, the national standard GB50217-91 "Power Engineering Cable Design Specification" specifies: dual protection current, voltage and DC power supply and trip control loop, etc. Two systems that require enhanced reliability should use separate control cables.

圖片3.png

After the control cable is put into operation, there is a problem of electrical interference between the different cores of the same cable and between the cables laid in parallel, and the main causes of electrical interference are:

(1) Electrostatic interference generated by the externally applied voltage on-line capacitive coupling between cores;

(2) Electromagnetic induction interference due to energization current. In general, when there is a high-voltage, high-current interference source nearby, the electrical interference is more serious. Because the distance between the cores of the same cable is small, the degree of interference is much greater than that of the parallel cable. For example, the control circuit of a phase-division operated circuit breaker of an ultra-high voltage substation, a three-phase combined cable, has had such an accident, the pulse of the phase separation operation causes the thyristors of other phases to be triggered, and the three-phase linkage is caused by mistake. With separate cables, no accidents occurred. Another example is the computer monitoring system of a power plant. Since a four-core cable is used to mix the analog low-level signal line with the power line of the transmitter, it has caused a 70V interference voltage on the signal line, which is in millivolts. The low level signal loop will obviously affect normal operation.

圖片4.png

Regarding the grounding method of the shielding layer, attention should be paid to the following points:

(1) The control cable shielding layer of the analog signal loop of the computer control system should be grounded at a centralized point. The reason is based on the requirement to ensure the normal operation of the computer monitoring system, because even the interference voltage of only about 1V may cause the logic judgment to be delayed, and the grounding circulation can be avoided by concentrating a little grounding;

(2) Except that the control cable shield of the computer monitoring system is only allowed to be grounded at one point, the other control cable shielding layer should be grounded at two points when the electromagnetic induction interference is large, and the interference caused by static induction is large. Then use a little grounding;

(3) The inner shield of the double shield or composite shield should be grounded at one point, and the outer shield can be grounded at two points;

(4) When selecting two points of grounding, it should also be considered that under the action of transient current, the shielding layer will not be burned.


Tags:
INQUIRY
主站蜘蛛池模板: 91国内精品久久久 | 日韩高清中文字幕一区二区 | 一区二区免费高清观看国产丝瓜 | 国产福利无码一区二区在线 | 老子午夜精品无码 | 在线免费小视频 | 欧美成人精品第一区 | 理论片午午伦夜理片影院99 | 一区二区免费在线视频 | 伊人精品久久 | 国产精品久久久久国产精品 | 欧美精品久久久久久久久老牛影院 | 欧美黄色aaaa | 国产公开免费人成视频 | 黄色日本在线观看 | 香蕉久久夜色精品国产尤物 | 国内精品美女A∨在线播放 国产做a爱一级久久 | 艳妇乳肉豪妇荡乳XXX | 国产美女在线精品 | 91国自产精品中文字幕亚洲 | 久久久噜噜噜久久熟女AA片 | 黑人玩弄人妻中文在线 | 黄片在线免费观看 | 亚洲乱亚洲乱妇24p 69久久国产露脸精品国产 | 视频国产一区二区 | 宅男666在线永久免费观看 | 免费XXXX大片| av狼最新网址 | 国产v片在线免费观看 | 久久久久女| 无遮无挡爽爽免费视频毛片韩国 | 亚洲国产精品原创巨作AV | 国产精品亚洲精品一区二区三区 | av在线播放资源 | 131美女爽爽爽爱做视频 | 被仇人调教成禁脔h虐莫 | 国产精品白丝JK白祙喷水视频 | 操大逼小说| 日韩国产精品无码一区二区三区 | 日本精品久久 | 国产甜淫av片免费观看 |